Split-phase electric power
A split-phase or single-phase three-wire system is a type of single-phase electric power distribution. It is the alternating current (AC) equivalent of the original Edison Machine Works three-wire direct-current system. Its primary advantage is that, for a given capacity of a distribution system, it saves conductor material over a single-ended single-phase system.[1]
The system is common in North America for residential and light commercial applications. Two 120 V AC lines are supplied to the premises that are out of phase by 180 degrees with each other (when both measured with respect to the neutral), along with a common neutral. The neutral conductor is connected to ground at the transformer center tap. Circuits for lighting and small appliance power outlets use 120 V circuits connected between one line and neutral. High-demand applications, such as ovens, are often powered using 240 V AC circuits—these are connected between the two 120 V AC lines. These 240 V loads are either hard-wired or use outlets which are deliberately non-interchangeable with 120 V outlets.
Other applications of a split-phase power system are used to reduce the electric shock hazard or to reduce electromagnetic noise.
Balanced power[edit]
In a so-called balanced power system, sometimes called "technical power", an isolation transformer with a center tap is used to create a separate supply with conductors at balanced voltages with respect to ground. The purpose of a balanced power system is to minimize the noise coupled into sensitive equipment from the power supply.
Unlike a three-wire distribution system, the grounded neutral is not distributed to the loads; only line-to-line connections at 120 V are used. A balanced power system is used only for specialized distribution in audio and video production studios, sound and television broadcasting, and installations of sensitive scientific instruments.
The U.S. National Electrical Code provides rules for technical power installations.[3] The systems are not to be used for general-purpose lighting or other equipment and may use special sockets to ensure that only approved equipment is connected to the system. Additionally, technical power systems pay special attention to the way the distribution system is grounded.
A risk of using a balanced power system, in an installation that also uses "conventional" power in the same rooms, is that a user may inadvertently interconnect the power systems together via an intermediate system of audio or video equipment, elements of which might be connected to different power systems. The chance of this happening may be reduced by appropriate labelling of the balanced power outlets and by the use of a type of power outlet socket for the balanced system that is physically different from that of the "conventional" power system to further differentiate them.
Applications[edit]
Europe[edit]
In Europe, three-phase 230/400 V is most commonly used. However, 130/225 V, three-wire, two-phase electric power discontinued systems called B1 are used to run old installations in small groups of houses when only two of the three-phase high-voltage conductors are used. The phase shift in Europe is 120°, as is the case with three-phase current. That's why we calculate 130V * √3 = 225V. A three-phase final step-down transformer is then used. One house gets phases A & B, the next house gets phase B & C, the third house gets phase A & C. Some installations, such as farms (especially those never subsequently upgraded to three-phase) may be supplied with both phases to the same consumer. Whilst usually metered through two chosen phases of a typical three-phase meter, these two phases will only ever be used individually, not, as in the USA, to provide a higher voltage. Nonetheless they help with situations where a single supply cannot provide enough power for an installation.
In the United Kingdom, electric tools and portable lighting at larger construction and demolition sites are governed by BS 7375, and where possible are recommended to be fed from a centre-tapped system with only 55 V between live conductors and the earth (so-called CTE or centre-tap earth, or 55–0–55). This reduced low-voltage system is used with 110 V equipment. No neutral conductor is distributed. In high-hazard locations, additional double-pole RCD protection may be used. The intention is to reduce the shock hazard that may exist when using electrical equipment at a wet or outdoor construction site, and eliminate the requirement for rapid automatic disconnection for prevention of shocks during faults. Portable transformers that transform single-phase 240 V to this 110 V split-phase system are a common piece of construction equipment. Generator sets used for construction sites are equipped to supply it directly. However, a large farm may be given a 230–0–230 (nominal) supply.
An incidental benefit is that the filaments of 110 V incandescent lamps used on such systems are thicker and thus mechanically more rugged than those of 240 V lamps.
North America[edit]
This three-wire single-phase system is common in North America for residential and light commercial applications. Circuit breaker panels typically have two live (hot) wires, and a neutral, connected at one point to the grounded center tap of a local transformer. Usually, one of the live wires is black and the other one red; the neutral wire is always white. Single-pole circuit breakers feed 120 V circuits from one of the 120 V buses within the panel, or two-pole circuit breakers feed 240-volt circuits from both buses. 120 V circuits are the most common, and used to power NEMA 1 and NEMA 5 outlets, and most residential and light commercial direct-wired lighting circuits. 240 V circuits are used for high-demand applications, such as air conditioners, space heaters, electric stoves, electric clothes dryers, water heaters, and electric vehicle charge points. These use NEMA 10 or NEMA 14 outlets that will not accept 120 V plugs.
Wiring regulations govern the application of split-phase circuits so that the shared neutral can be protected from excess current. A neutral wire can be shared only by two circuits fed from opposite lines of the supply system, using circuit breakers connected by a bar so that both trip simultaneously ([4] NEC 210.4); this prevents 120 V from feeding across 240 V circuits.
Railways[edit]
In the electric power supply system of railways in Sweden split-phase electric power is also used on some railways. The center tap is grounded and one pole is fed to an overhead wire section, while the other wire is used for another section.
Split-phase distribution is used on Amtrak's 60 Hz traction power system in the Northeast Corridor between New York and Boston. Two separate wires are run along the track, the contact wire for the locomotive and an electrically separate feeder wire. Each wire is fed with 25 kV with respect to ground, with 50 kV between them. Autotransformers along the track balance the loads between the contact and feeder wires, reducing resistive losses.